Vulnérabilité moyenne dans APOGEE PXC Compact (BACnet) (Siemens)
Description
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
Gravité et risque d'exploitation
CVE-2020-28388 obtient un score CVSS de 6.5/10, soit une gravité moyenne. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 1.35 %, ce qui la place devant 71.0 % des CVE référencées.
Que faire ?
- Vérifiez si APOGEE PXC Compact (BACnet) (versions All versions < V2012.12, All versions < V3.5.5, All versions < V5.2, All versions, All versions < V2.8.20) est présent sur votre parc.
- Appliquez le correctif ou la version corrigée indiqués dans les références de l'éditeur.
- À défaut de correctif, limitez l'exposition (filtrage réseau, désactivation du composant).
- Automatisez la détection : les agents CVE Heimdall (gratuits, open source) corrèlent l'inventaire de vos serveurs avec la base CVE.