CVE-2020-28397

Vulnérabilité non évaluée dans SIMATIC Drive Controller family (Siemens)

CVSS 0.0 · Non évaluée
EPSS 0.8%
Siemens•SIMATIC Drive Controller family•Versions : Version V2.1, All versions < V2.9.2, All versions > V2.5 < V2.9.2, All versions > V2 < V4, All versions > V2.5 < V21.9, All versions < V21.9, Version V4.4

Description

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7 PLCSIM Advanced (All versions > V2 < V4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (Version V4.4), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions > V2.5 < V2.9.2), SIMATIC S7-1500 Software Controller (All versions > V2.5 < V21.9), TIM 1531 IRC (incl. SIPLUS NET variants) (Version V2.1). Due to an incorrect authorization check in the affected component, an attacker could extract information about access protected PLC program variables over port 102/tcp from an affected device when reading multiple attributes at once.

Gravité et risque d'exploitation

CVE-2020-28397 obtient un score CVSS de 0.0/10, soit une gravité non évaluée. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 0.75 %, ce qui la place devant 54.1 % des CVE référencées.

Que faire ?

  • Vérifiez si SIMATIC Drive Controller family (versions Version V2.1, All versions < V2.9.2, All versions > V2.5 < V2.9.2, All versions > V2 < V4, All versions > V2.5 < V21.9, All versions < V21.9, Version V4.4) est présent sur votre parc.
  • Appliquez le correctif ou la version corrigée indiqués dans les références de l'éditeur.
  • À défaut de correctif, limitez l'exposition (filtrage réseau, désactivation du composant).
  • Automatisez la détection : les agents CVE Heimdall (gratuits, open source) corrèlent l'inventaire de vos serveurs avec la base CVE.

Références