CVE-2022-2502

Vulnérabilité élevée dans RTU500 series (Hitachi Energy)

CVSS 7.5 · Élevée
EPSS 0.6%
Hitachi Energy•RTU500 series•Versions : RTU500 series CMU Firmware version 13.3.2, RTU500 series CMU Firmware version 13.3.3, RTU500 series CMU Firmware version 13.4.1, RTU500 series CMU Firmware version 13.3.1

Description

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.

Gravité et risque d'exploitation

CVE-2022-2502 obtient un score CVSS de 7.5/10, soit une gravité élevée. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 0.65 %, ce qui la place devant 49.9 % des CVE référencées.

Que faire ?

  • Vérifiez si RTU500 series (versions RTU500 series CMU Firmware version 13.3.2, RTU500 series CMU Firmware version 13.3.3, RTU500 series CMU Firmware version 13.4.1, RTU500 series CMU Firmware version 13.3.1) est présent sur votre parc.
  • Appliquez le correctif ou la version corrigée indiqués dans les références de l'éditeur.
  • À défaut de correctif, limitez l'exposition (filtrage réseau, désactivation du composant).
  • Automatisez la détection : les agents CVE Heimdall (gratuits, open source) corrèlent l'inventaire de vos serveurs avec la base CVE.

Références