CVE-2022-30314

Vulnérabilité non évaluée

CVSS 0.0 · Non évaluée
EPSS 0.3%

Description

Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).

Gravité et risque d'exploitation

CVE-2022-30314 obtient un score CVSS de 0.0/10, soit une gravité non évaluée. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 0.29 %, ce qui la place devant 20.5 % des CVE référencées.