CVE-2022-30317
Vulnérabilité non évaluée
Description
Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.
Gravité et risque d'exploitation
CVE-2022-30317 obtient un score CVSS de 0.0/10, soit une gravité non évaluée. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 0.87 %, ce qui la place devant 58.1 % des CVE référencées.
Que faire ?
- Vérifiez si le produit concerné est présent sur votre parc.
- Appliquez le correctif ou la version corrigée indiqués dans les références de l'éditeur.
- À défaut de correctif, limitez l'exposition (filtrage réseau, désactivation du composant).
- Automatisez la détection : les agents CVE Heimdall (gratuits, open source) corrèlent l'inventaire de vos serveurs avec la base CVE.