CVE-2025-54850

Vulnérabilité élevée dans DIRIS Digiware M-70 (Socomec)

CVSS 7.5 · Élevée
EPSS 0.3%
Socomec•DIRIS Digiware M-70•Versions : 1.6.9

Description

A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus RTU over TCP messages to port 503 using the Write Single Register function code (6). The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change. After this configuration change, the device will be in a denial-of-service state.

Gravité et risque d'exploitation

CVE-2025-54850 obtient un score CVSS de 7.5/10, soit une gravité élevée. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 0.32 %, ce qui la place devant 23.6 % des CVE référencées.

Que faire ?

  • Vérifiez si DIRIS Digiware M-70 (versions 1.6.9) est présent sur votre parc.
  • Appliquez le correctif ou la version corrigée indiqués dans les références de l'éditeur.
  • À défaut de correctif, limitez l'exposition (filtrage réseau, désactivation du composant).
  • Automatisez la détection : les agents CVE Heimdall (gratuits, open source) corrèlent l'inventaire de vos serveurs avec la base CVE.

Références