CVE-2026-3611

Vulnérabilité critique dans IQ4E (Honeywell)

CVSS 10.0 · Critique
EPSS 1.0%
Honeywell•IQ4E•Versions : <=4.36 (build 4.3.7.9), v3.50_3.44

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Gravité et risque d'exploitation

CVE-2026-3611 obtient un score CVSS de 10.0/10, soit une gravité critique. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 1.03 %, ce qui la place devant 62.9 % des CVE référencées.

Que faire ?

  • Vérifiez si IQ4E (versions <=4.36 (build 4.3.7.9), v3.50_3.44) est présent sur votre parc.
  • Appliquez le correctif ou la version corrigée indiqués dans les références de l'éditeur.
  • À défaut de correctif, limitez l'exposition (filtrage réseau, désactivation du composant).
  • Automatisez la détection : les agents CVE Heimdall (gratuits, open source) corrèlent l'inventaire de vos serveurs avec la base CVE.

Références