CVE-2026-3611
Vulnérabilité critique dans IQ4E (Honeywell)
Description
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Gravité et risque d'exploitation
CVE-2026-3611 obtient un score CVSS de 10.0/10, soit une gravité critique. Selon le modèle EPSS, la probabilité qu'elle soit exploitée dans les 30 prochains jours est de 1.03 %, ce qui la place devant 62.9 % des CVE référencées.
Que faire ?
- Vérifiez si IQ4E (versions <=4.36 (build 4.3.7.9), v3.50_3.44) est présent sur votre parc.
- Appliquez le correctif ou la version corrigée indiqués dans les références de l'éditeur.
- À défaut de correctif, limitez l'exposition (filtrage réseau, désactivation du composant).
- Automatisez la détection : les agents CVE Heimdall (gratuits, open source) corrèlent l'inventaire de vos serveurs avec la base CVE.